HomeMy WebLinkAbout2026-01-14 - Solar Site Plan 24.75KWDRAWN BY:
Customer Information
Manuel Pesantes
Residence
3611 Gomer St, Yorktown
Heights, NY 10598, USA
DATE:
DG
01/14/2026
DIRECTORY OF PAGES
PV - 1 TITLE PAGE
PV - 2 SITE PLAN
PV - 3 ATTACHMENT PLAN
PV - 4 3-LINE DIAGRAM
PV - 5 SAFETY LABELS
DATASHEETS
INVERTER DATASHEET
MOUNTING SYSTEM DATASHEET
GENERAL NOTE
THE SCOPE OF THIS PROJECT INVOLVES THE
PLACEMENT OF SOLAR PANELS, WHICH WILL BE
SECURED USING A PRE-DESIGNED RACKING
SYSTEM. AFTER BEING ARRANGED ON THE RACKS,
THE SOLAR MODULES WILL BE JOINED TOGETHER
USING DC TO AC POWER INVERTERS, AND THEN
LINKED TO THE LOCAL UTILITY THROUGH METHODS
THAT COMPLY WITH THE REGULATIONS IMPOSED BY
THE UTILITY AND THE JURISDICTION RESPONSIBLE
FOR ISSUING PERMITS.
SITE LAYOUT
INTERCONNECTION DETAILS
POINT OF CONNECTION
( AC
CONNECTION PER NEC
ARTICLE 705.12(D)
UTILITY SERVICE 120 / 240 V
ELECTRICAL PANEL
MAIN SERVICE PANEL
W/TOP-FED
BUSBAR, MAIN
BREAKER
SYSTEM DETAILS
DESCRIPTION
NEW GRID-INTERACTIVE
PHOTOVOLTAIC SYSTEM
WITH NO BATTERY
STORAGE
DC RATING OF SYSTEM
AC RATING OF SYSTEM
INVERTER(S)( ) ENPHASE IQ8MC
(240 V)
INVERTER TYPE MICRO INVERTER
MODULE ( )
PROJECT DETAILS
ZONING RESIDENTIAL
USE AND OCCUPANCY
CLASSIFICATION
SINGLE FAMILY
DWELLING
PERMITTING AUTHORITY
UTILITY COMPANY
METER SERIAL NUMBER
NEC VERSION 2017 NEC (NFPA 70)
FIRE CODE 2020 NYS RESIDENTIAL
CODE, IBC 2015.
Engineering Seal:
13 Trade Zone Drive,
Ronkonkoma, NY
11779 Unit #13
PV - 6
PANEL DATASHEET
PAGE:1, PROJECT SUMMARY
SITE DETAILS
ASHRAE EXTREME LOW F
ASHRAE 2% HIGH F
CLIMATE DATA SOURCE TMY3
WIND SPEED MPH
WIND EXPOSURE
CATEGORY B
GROUND SNOW LOAD PSF
45
45
SEG-550-BMA-BG
CONEDISON
200A
200A
-7.6°
130
40
24,750 W
14,400 W
LINE SIDE
91.4°
DRAWN BY:
Customer Information
Manuel Pesantes
Residence
3611 Gomer St, Yorktown
Heights, NY 10598, USA
DATE:
DG
01/14/2026
R324.6 ROOF ACCESS AND PATHWAYS - ROOF ACCESS, PATHWAYS, AND SETBACK REQUIREMENTS SHALL BE PROVIDED IN ACCORDANCE WITH SECTIONS R324.6.1 THROUGH R.324.6.2.1. ACCESS AND MINIMUM SPACING SHALL BE
REQUIRED TO PROVIDE EMERGENCY ACCESS TO THE ROOF, TO PROVIDE PATHWAYS TO SPECIFIC AREAS OF THE ROOF, PROVIDE FOR SMOKE VENTILATION OPPORTUNITY AREAS, AND TO PROVIDE EMERGENCY EGRESS FROM THE
ROOF.
EXCEPTIONS:
1. DETACHED, UNINHABITABLE STRUCTURES, INCLUDING BUT NOT LIMITED TO DETACHED GARAGES, PARKING SHADE STRUCTURES, CARPORTS, SOLAR TRELLISES AND SIMILAR STRUCTURES, SHALL NOT BE REQUIRED TO
PROVIDE ROOF ACCESS.
2. ROOF ACCESS, PATHWAYS AND SETBACKS NEED NOT BE PROVIDED WHERE THE BUILDING OFFICIAL HAS DETERMINED THAT ROOFTOP OPERATIONS WILL NOT BE EMPLOYED.
3. THESE REQUIREMENTS SHALL NOT APPLY TO ROOFS WITH SLOPES OF TWO UNITS VERTICAL IN 12 UNITS HORIZONTAL (17-PERCENT SLOPE) OR LESS.
(NY) R324.6.1 PATHWAYS - NOT FEWER THAN TWO PATHWAYS, ON SEPARATE ROOF PLANES FROM LOWEST ROOF EDGE TO RIDE AND NOT LESS THAN 36 INCHES (914MM) WIDE, SHALL BE PROVIDED ON ALL BUILDINGS. NOT FEWER
THAN ONE PATHWAY SHALL BE PROVIDED ON THE STREET OR DRIVEWAY SIDE OF THE ROOF. FOR EACH ROOF PLANE WITH A PHOTOVOLTAIC ARRAY, A PATHWAY NOT LESS THAN 36 INCHES WIDE (914MM) SHALL BE PROVIDED FROM
THE LOWEST ROOF EDGE TO RIDGE ON THE SAME ROOF PLANE AS THE PHOTOVOLTAIC ARRAY, ON AN ADJACENT ROOF PLANE, OR STRADDLING THE SAME AND ADJACENT ROOF PLANES. PATHWAYS SHALL BE OVER AREAS CAPABLE
OF SUPPORTING FIRE FIGHTERS ACCESSING THE ROOF. PATHWAYS SHALL BE LOCATED IN AREAS WITH MINIMAL OBSTRUCTIONS SUCH AS VENT PIPES, CONDUIT, OR MECHANICAL EQUIPMENT. PATHWAYS ON OPPOSING ROOF
SLOPES SHALL NOT BE LOCATED ALONG THE SAME PLANE AS THE TRUSS, RAFTER, OR OTHER SUCH FRAMING SYSTEM THAT SUPPORTS THE PATHWAY.
EXCEPTION: ACCESS PATHWAYS SHALL NOT BE REQUIRED ON ROOF SLOPES CONTAINING PHOTOVOLTAIC MODULES, PANELS, OR AN ARRAY WHERE THE OPPOSING OR ADJACENT ROOF SLOPE IS AN ACCESS ROOF.
(NY) R324.6.2 SETBACK AT RIDGE - PHOTOVOLTAIC ARRAYS SHALL NOT BE LOCATED LESS THAN 18 INCHES (457MM) FROM A HORIZONTAL RIDGE.
GENERAL NOTES
1
THE CONTRACTOR SHALL USE ONLY COMPONENTS
LISTED BY A NATIONALLY RECOGNIZED TESTING
LABORATORY FOR THE INTENDED USE.
2
THE CONTRACTOR IS ACCOUNTABLE FOR PROVIDING
ALL NECESSARY EQUIPMENT, CABLES, ADDITIONAL
CONDUITS, BOXES, RACEWAYS, AND OTHER
ACCESSORIES REQUIRED TO ENSURE A FULLY
FUNCTIONAL AND OPERATIONAL PV SYSTEM.
3
EQUIPMENT LIKELY TO BE WORKED UPON WHILE
ENERGIZED SHALL BE INSTALLED IN LOCATIONS THAT
SATISFY MINIMUM WORKING CLEARANCES PER NEC
110.26
4
THE SYSTEM MUST SATISFY THE NEC ARTICLE 690,
ADHERE TO ALL MANUFACTURERS' LISTING AND
INSTALLATION GUIDELINES, AND COMPLY WITH THE
PERTINENT CODES AS STATED BY THE AUTHORITY
HAVING JURISDICTION'S (AHJ) RELEVANT
REGULATIONS.
5
IF A DC PV SOURCE OR DC PV OUTPUT CIRCUITS ARE
ROUTED WITHIN THE BUILDING, THEY MUST BE
ENCLOSED IN METAL RACEWAYS, TYPE MC
METAL-CLAD CABLE, OR METAL ENCLOSURES FROM
THE POINT OF ENTRY INTO THE BUILDING UP TO THE
INITIAL DISCONNECTING MECHANISM READILY
ACCESSIBLE, AS PER NEC 690.31(G).
Engineering Seal:
13 Trade Zone Drive,
Ronkonkoma, NY
11779 Unit #13
SCALE 1/32" = 1'-0
PAGE:2, SITE PLAN
FR
O
N
T
O
F
H
O
U
S
E
,
F
A
C
I
N
G
S
T
R
E
E
T
MICRO INVERTERS
UNDER MODULES
(45) PV ARRAY
GROUND MOUNT
SYSTEM FACING SOUTH
MAIN HOUSE
D M
D
UTILITY METER
MAIN SERVICE PANEL
PV AC COMBINER
BOX W MONITORING
AC DISCONNECT
AC DISCONNECT
± 28'-7'' TRENCHED
CONDUIT
TRENCHED/OVEHEAD G
O
M
E
R
S
T
POOL
EXISTING PROPERTY LINE
NEIGHBOUR HOUSE
NEIGHBOUR HOUSE
DRAWN BY:
Customer Information
Manuel Pesantes
Residence
3611 Gomer St, Yorktown
Heights, NY 10598, USA
DATE:
DG
01/14/2026
NOTE
·AN 18" WIDE CLEARING (FREE OF SOLAR EQUIPMENT) SHALL BE PROVIDED ALONG AT LEAST ONE
SIDE OF THE ROOF RIDGE ON THE SAME SIDE AS THE SOLAR EQUIPMENT OR ON ANOTHER SIDE OF
THE RIDGE THAT DOES NOT HAVE SOLAR EQUIPMENT ON IT. SUFFICIENT ACCESS PATHWAYS, ROOF
ACCESS POINTS, AND GROUND ACCESS AREAS SHALL BE PROVIDED IN ACCORDANCE WITH THE
2020 NYS RESIDENTIAL CODE.
·ROOF SHALL HAVE NO MORE THAN A SINGLE LAYER OF ROOF COVERING IN ADDITION TO THE SOLAR
EQUIPMENT.
·INSTALLATION OF SOLAR EQUIPMENT SHALL BE FLUSH-MOUNTED, PARALLEL TO AND NO MORE
THAN 6-INCHES ABOVE THE SURFACE OF THE ROOF.
·WEIGHT OF THE INSTALLED SYSTEM SHALL NOT EXCEED MORE THAN 5-PSF.
·ANY PLUMBING VENTS ARE NOT TO BE CUT OR COVERED FOR SOLAR EQUIPMENT INSTALLATION.
ANY RELOCATION OR MODIFICATION OF THE VENT REQUIRES A PLUMBING PERMIT AND INSPECTION.
THIS PV SYSTEM HAS BEEN DESIGNED TO MEET THE MINIMUM DESIGN STANDARDS FOR BUILDING AND
OTHER STRUCTURES OF THE ASCE 7-16, 2020 NYS RESIDENTIAL CODE.
Engineering Seal:
13 Trade Zone Drive,
Ronkonkoma, NY
11779 Unit #13
SCALE 3/32" = 1'-0
PAGE:3, ATTACHMENT PLAN
"RAIL END OVERHANG"
DISTANCE FROM RAIL END
TO OUTER ROOF ATTACHMENT CENTER.
NOT TO EXCEED 34% OF ALLOWABLE SPAN
STRUCTURAL MEMBER
"RAIL SPAN" DISTANCE BETWEEN
CENTERS OF TWO ROOF ATTACHMENTS
BA
PV MODULE, TYP.
C
MID CLAMP ASSEMBLY
SS BONDING PIN
MODULE
FRAME
RAIL
CHANNEL NUT
6-12 AWG BARE
COPPER WIRE
5/16"-18 SS BOLT
SS SPLIT LOCK WASHER
(TORQUE TO 16 FT-LBS)
SNAPNRACK
GROUND LUG
CHANNEL NUT
RAIL
SS BONDING
PINS
ARRAY1
180° TRUE; 30° TILT;
7/12 PITCH
(45) MODULES 1/2" SPACING BETWEEN
ROWS AND COLUMNS
DRAWN BY:
Customer Information
Manuel Pesantes
Residence
3611 Gomer St, Yorktown
Heights, NY 10598, USA
DATE:
DG
01/14/2026
Engineering Seal:
13 Trade Zone Drive,
Ronkonkoma, NY
11779 Unit #13
PAGE:3, ATTACHMENT PLAN
DRAWN BY:
Customer Information
Manuel Pesantes
Residence
3611 Gomer St, Yorktown
Heights, NY 10598, USA
DATE:
DG
01/14/2026
Engineering Seal:
13 Trade Zone Drive,
Ronkonkoma, NY
11779 Unit #13
PAGE:4, LINE DIAGRAM
GENERAL NOTES
1 ALL MODULES WILL BE GROUNDED IN ACCORDANCE WITH CODE AND THE MANUFACTURER'S
INSTALLATION INSTRUCTIONS
2 ALL PV EQUIPMENT SHALL LISTED BY RECOGNIZED TESTING LAB
3 WHEN A BACKFEED BREAKER IS METHOD OF UTILITY INTERCONNECTION, BREAKER SHALL NOT
READ LINE AND LOAD
4 WHEN A BACKFEED BREAKER IS METHOD OF UTILITY INTERCONNECTION, THE BREAKER SHALL BE
INSTALLED AT THE OPPOSITE END OF THE BASS BAR OF THE MAIN BREAKER
5 WORK CLEARANCE AROUND ELECTRICAL EQUIPMENT WILL BE MAINTAINED PER NEC 110.26(A)(1),
110.26(A)(2), 110.269(A)(3)
6 ALL EXTERIOR CONDUITS, FITTINGS AND BOXES SHALL BE RAIN TIGH AND BE MIN. NEMA 3R RATED
7 AC AND DC GROUNDING CONDUCTORS PER NEX ARTICLE 690.43(A) THRU (F) CONNECTED AS PER
690.45(A), 690.46 AND SIZED PER 250.112
8 PROVIDE EXPANSION JOINTS AND ANCHORING OF ALL CONDUIT RUNS AS PER NEC REQUIREMENTS
9
PROVIDE LABEL, PLACARD AT EXISTING UTILITY CONNECTION WITH "WARNING - CUSTOMER OWNED
ELECTRICAL GENERATION EQUIPMENT CONNECTED" WITH APPROPRIATE HAZARD AND OUTPUT
RAITING OF PV SYSTEM
15A/2P
N L2 L1
IQ COMBINER PANEL
ENPHASE ENVOY
20A/2P
EGC ATTACHED
TO RAIL
1 2
ATTICROOF
SOLAR DECK
1 2
20A/2P
100A RATED
AC DISCONNECT
80A RATED FUSES
98
7
EXTERIOR WALL
20A/2P
1 2
EGC ATTACHED
TO RAIL
3 4
ATTICROOF
SOLAR DECK
1 2
20A/2P
5 6
ATTICROOF
SOLAR DECK12
20A/2P
EGC ATTACHED
TO RAIL
NUMBER
OF
CONDUC
TORS
CONDUCT SIZE
ENPHASE Q-CABLE 12 4 N/A N/A 100'-0"
BARE COPPER GND
IN FREE AIR 6 1 N/A N/A 35'-0"
2 THHN 10 4 LFMC & PVC 1"40'-0"
3 ENPHASE Q-CABLE 12 4 PVC SCH. 40 1"100'-0"
BARE COPPER GND
IN FREE AIR 6 1 PVC SCH. 40 1"35'-0"
4 THHN 10 4 LFMC & PVC 1"40'-0"
5 ENPHASE Q-CABLE 12 2 PVC SCH. 40 1"100'-0"
BARE COPPER GND
IN FREE AIR 6 1 PVC SCH. 40 1"35'-0"
6 THHN 10 2 LFMC & PVC 1"40'-0"
7 THHN 10 10 PVC SCH. 40 1"25'-0"
EGC 10 2 PVC SCH. 40 1"25'-0"
8 THHN 4 3 PVC SCH. 40 1"20'-0"
EGC 4 1 PVC SCH. 40 1"20'-0"
9 THHN 4 3 PVC SCH. 40 1"20'-0"
GEC 4 1 RMC 1"20'-0"
1 2
MAIN
LOADS
NOTE:
THIS MAIN DISTRIBUTION PANEL
HAS A RATED BUS WITH
MAIN BREAKER
BUS x 120% =
- MAIN =
THE MAXIMUM BACK FEED CIRCUIT
BREAKER SIZE IS PER NEC
2017 SECTION 705.12(D)(2)(3)(b)
CONNECTION WITH
LINE SIDE TAP PER NEC 2017
SECTION 230.82(6)
LINE SIDE
TAP
200A
200A200A
200A 240 A
240 A 200A 40 A
40 A
STRING OF
(9)
(9) ENPHASE IQ8MC-72-M-US
MICRO INVERTER
IN PARALLEL
9 MODULES/STRING x 1.33 A/MODULE = 11.97 AMP LOAD/STRING
11.97 AMP x 1.25 CONT DUTY = 14.96 AMP (WIRE AMPACITY MIN.)
98
SEG-550-BMA-BG
STRING OF
(9)
(9) ENPHASE IQ8MC-72-M-US
MICRO INVERTER
IN PARALLEL
9 MODULES/STRING x 1.33 A/MODULE = 11.97 AMP LOAD/STRING
11.97 AMP x 1.25 CONT DUTY = 14.96 AMP (WIRE AMPACITY MIN.)
98
SEG-550-BMA-BG
STRING OF
(9)
(9) ENPHASE IQ8MC-72-M-US
MICRO INVERTER
IN PARALLEL
9 MODULES/STRING x 1.33 A/MODULE = 11.97 AMP LOAD/STRING
11.97 AMP x 1.25 CONT DUTY = 14.96 AMP (WIRE AMPACITY MIN.)
98
SEG-550-BMA-BG
STRING OF
(9)
(9) ENPHASE IQ8MC-72-M-US
MICRO INVERTER
IN PARALLEL
9 MODULES/STRING x 1.33 A/MODULE = 11.97 AMP LOAD/STRING
11.97 AMP x 1.25 CONT DUTY = 14.96 AMP (WIRE AMPACITY MIN.)
98
SEG-550-BMA-BG
STRING OF
(9)
(9) ENPHASE IQ8MC-72-M-US
MICRO INVERTER
IN PARALLEL
9 MODULES/STRING x 1.33 A/MODULE = 11.97 AMP LOAD/STRING
11.97 AMP x 1.25 CONT DUTY = 14.96 AMP (WIRE AMPACITY MIN.)
98
SEG-550-BMA-BG
DRAWN BY:
Customer Information
Manuel Pesantes
Residence
3611 Gomer St, Yorktown
Heights, NY 10598, USA
DATE:
DG
01/14/2026
Engineering Seal:
13 Trade Zone Drive,
Ronkonkoma, NY
11779 Unit #13
PAGE:4, LINE DIAGRAM
GENERAL NOTES
1 ALL MODULES WILL BE GROUNDED IN ACCORDANCE WITH CODE AND THE MANUFACTURER'S
INSTALLATION INSTRUCTIONS
2 ALL PV EQUIPMENT SHALL LISTED BY RECOGNIZED TESTING LAB
3 WHEN A BACKFEED BREAKER IS METHOD OF UTILITY INTERCONNECTION, BREAKER SHALL NOT
READ LINE AND LOAD
4 WHEN A BACKFEED BREAKER IS METHOD OF UTILITY INTERCONNECTION, THE BREAKER SHALL BE
INSTALLED AT THE OPPOSITE END OF THE BASS BAR OF THE MAIN BREAKER
5 WORK CLEARANCE AROUND ELECTRICAL EQUIPMENT WILL BE MAINTAINED PER NEC 110.26(A)(1),
110.26(A)(2), 110.269(A)(3)
6 ALL EXTERIOR CONDUITS, FITTINGS AND BOXES SHALL BE RAIN TIGH AND BE MIN. NEMA 3R RATED
7 AC AND DC GROUNDING CONDUCTORS PER NEX ARTICLE 690.43(A) THRU (F) CONNECTED AS PER
690.45(A), 690.46 AND SIZED PER 250.112
8 PROVIDE EXPANSION JOINTS AND ANCHORING OF ALL CONDUIT RUNS AS PER NEC REQUIREMENTS
9
PROVIDE LABEL, PLACARD AT EXISTING UTILITY CONNECTION WITH "WARNING - CUSTOMER OWNED
ELECTRICAL GENERATION EQUIPMENT CONNECTED" WITH APPROPRIATE HAZARD AND OUTPUT
RAITING OF PV SYSTEM
IQ COMBINER
PANEL
100A RATED
AC DISCONNECT
80A RATED FUSESSOLAR DECK
1 2
ATTICROOF
54
NUMBER
OF
CONDUC
TORS
CONDUCT SIZE
ENPHASE Q-CABLE 12 4 N/A N/A 100'-0"
BARE COPPER GND
IN FREE AIR 6 1 N/A N/A 35'-0"
2 THHN 10 4 LFMC & PVC 1"40'-0"
3 ENPHASE Q-CABLE 12 4 PVC SCH.
40 1"100'-0"
BARE COPPER GND
IN FREE AIR 6 1 PVC SCH.
40 1"35'-0"
4 THHN 10 4 LFMC & PVC 1"40'-0"
5 ENPHASE Q-CABLE 12 2 PVC SCH.
40 1"100'-0"
BARE COPPER GND
IN FREE AIR 6 1 PVC SCH.
40 1"35'-0"
6 THHN 10 2 LFMC & PVC 1"40'-0"
7 THHN 10 10 PVC SCH.
40 1"25'-0"
EGC 10 2 PVC SCH.
40 1"25'-0"
8 THHN 4 3 PVC SCH.
40 1"20'-0"
EGC 4 1 PVC SCH.
40 1"20'-0"
9 THHN 4 3 PVC SCH.
40 1"20'-0"
GEC 4 1 RMC 1"20'-0"
MSP
BUSBAR
200A
200A
DC
AC
24,750 W
14,400 W
STRING OF
(9)
(9) ENPHASE IQ8MC-72-2-US
MICRO INVERTER
IN PARALLEL
SEG-550-BMA-BG
STRING OF
(9)
(9) ENPHASE IQ8MC-72-2-US
MICRO INVERTER
IN PARALLEL
SEG-550-BMA-BG
STRING OF
(9)
(9) ENPHASE IQ8MC-72-2-US
MICRO INVERTER
IN PARALLEL
SEG-550-BMA-BG
STRING OF
(9)
(9) ENPHASE IQ8MC-72-2-US
MICRO INVERTER
IN PARALLEL
SEG-550-BMA-BG
STRING OF
(9)
(9) ENPHASE IQ8MC-72-2-US
MICRO INVERTER
IN PARALLEL
SEG-550-BMA-BG
DRAWN BY:
Customer Information
Manuel Pesantes
Residence
3611 Gomer St, Yorktown
Heights, NY 10598, USA
DATE:
DG
01/14/2026
1 NEC ARTICLE 690.31(G)(3)
2 AT THE EACH DISCONNECTING
MEANS FOR PHOTOVOLTAIC
EQUIPMENT. NEC ARTICLE
690.17(4)
3 AT EACH DEVICE WHERE
ENERGIZED, UNGROUNDED
CIRCUITS MAY BE EXPOSED
DURING SERVICE. NEC ARTICLE
690.35(F)
4 DC DISCONNECT, NEC ARTICLE
690.53 (FOR REFERENCE ONLY)
5 AC DISCONNECT, NEC ARTICLE
690.54 (FOR REFERENCE ONLY)
6 NEC ARTICLE 690.56(C)
7 SOLAR BREAKER (MSP) NEC
ARTICLE 705.12(D)(2)(3)(B)
8 ANY AC ELECTRICAL PANEL
THAT IS FEED BY BOTH THE
UTILITY AND THE
PHOTOVOLTAIC SYSTEM (MSP)
NEC ARTICLE 705.12(D)(4)
Engineering Seal:
13 Trade Zone Drive,
Ronkonkoma, NY
11779 Unit #13
9 PLACED ON ALL INTERIOR
AND EXTERIOR DC
CONDUIT, RACEWAYS,
ENCLOSURES, AND CABLE
ASSEMBLIES AT LEAST
EVERY 10 FEET
IFC603.11.1.4
LABELING NOTES
1 ALL PLAQUES AND SIGNAGE REQUIRED BY 2017 NEC
WILL BE INSTALLED AS REQUIRED
2
IT IS REQUIRED TO PLACE WARNING LABELS ON EACH
DC RACEWAY EVERY 10 FEET, AS WELL AS WITHIN
ONE FOOT OF EVERY TURN OR BEND, AND ONE FOOT
ABOVE AND BELOW ANY PENETRATION OF
ROOF/CEILING ASSEMBLIES, WALLS, OR BARRIERS.
THESE LABELS MUST CONTAIN THE MARKING
"WARNING: PHOTOVOLTAIC POWER SOURCE" AND
HAVE 3/8" TALL LETTERS. THE LABEL MUST BE
REFLECTIVE WITH WHITE TEXT ON A RED
BACKGROUND.
3
A PERMANENT PLAQUE OR DIRECTORY MUST BE
INSTALLED TO INDICATE THE LOCATION OF THE
SERVICE DISCONNECTING MEANS AND THE
PHOTOVOLTAIC SYSTEM DISCONNECTING MEANS, IF
THEY ARE NOT IN THE SAME LOCATION. THIS IS TO
ENSURE COMPLIANCE WITH NEC 690.56(B).
4
LABEL(S) WITH MARKING "SOLAR PV SYSTEM
EQUIPPED WITH RAPID SHUTDOWN." SHALL BE
LOCATED POINT-OF-INTERCONNECTION OR AT MAIN
SERVICE DISCONNECT. THE LABEL SHALL HAVE 3/8"
TALL LETTERS AND BE REFLECTIVE WITH WHITE TEXT
ON A RED BACKGROUND
5
IF THE INVERTERS ARE REMOTELY LOCATED FROM
ONE ANOTHER, DIRECTORIES MUST BE INSTALLED AT
EACH DC PHOTOVOLTAIC SYSTEM DISCONNECTING
MEANS, AC IS CONNECTING MEANS, AND MAIN
SERVICE DISCONNECTING MEANS. THESE
DIRECTORIES MUST SHOW THE LOCATION OF ALL AC
AND DC PHOTOVOLTAIC SYSTEM DISCONNECTING
MEANS IN THE BUILDING, IN ACCORDANCE WITH NEC
690.4(H).
6
ALL LABELS, WARNINGS, AND MARKINGS MUST
FOLLOW ANSI Z535.4 REGULATIONS. THIS REQUIRES
THE USE OF DANGER, WARNING, AND CAUTION SIGNS
WITH STANDARD HEADER COLORS, HEADER TEXT,
AND SAFETY ALERT SYMBOL ON EACH LABEL. THE
ANSI STANDARD ALSO DEMANDS A HEADING THAT IS
AT LEAST 50% TALLER THAN THE BODY TEXT, AS
SPECIFIED BY NEC ARTICLE 110.21(B) i.
7
THE MATERIALS USED FOR MARKING MUST BE
WEATHER RESISTANT, IN COMPLIANCE WITH CBC
511.3.1. IT IS RECOMMENDED THAT UL 969 BE USED
AS STANDARD TO DETERMINE WEATHER RATING
PAGE:5, SAFETY LABELS
DRAWN BY:
Customer Information
Manuel Pesantes
Residence
3611 Gomer St, Yorktown
Heights, NY 10598, USA
DATE:
DG
01/14/2026
Engineering Seal:
13 Trade Zone Drive,
Ronkonkoma, NY
11779 Unit #13
PAGE:6, DATASHEETS
DRAWN BY:
Customer Information
Manuel Pesantes
Residence
3611 Gomer St, Yorktown
Heights, NY 10598, USA
DATE:
DG
01/14/2026
Engineering Seal:
13 Trade Zone Drive,
Ronkonkoma, NY
11779 Unit #13
PAGE:6, DATASHEETS
DRAWN BY:
Customer Information
Manuel Pesantes
Residence
3611 Gomer St, Yorktown
Heights, NY 10598, USA
DATE:
DG
01/14/2026
Engineering Seal:
13 Trade Zone Drive,
Ronkonkoma, NY
11779 Unit #13
PAGE:6, DATASHEETS
DRAWN BY:
Customer Information
Manuel Pesantes
Residence
3611 Gomer St, Yorktown
Heights, NY 10598, USA
DATE:
DG
01/14/2026
Engineering Seal:
13 Trade Zone Drive,
Ronkonkoma, NY
11779 Unit #13
PAGE:6, DATASHEETS